Load Regulation : 1% (300mV from 10% to 100% load change measured on sense terminal
Ripple &Noise : 0.5% (150mV Pk - Pk when measured with shortest probe lead length and 0.1uF/63V ceramic capacitor paralleled with 100uF/63V electrolytic capacitor across the probe tip.
Efficiency : Better than 80%
Power Factor : 0.9
Indication : Power ON, DC OK, C/L, I/P U/V, I/P O/V, O/T
Output Voltage Adj. : + 2V by front panel Vadj pot
Current Limit (CC type) : 70~72A
Output Over Voltage : 33V to 35V (Check at 10% load. (trip type) mains recycling required to restart SMPS after removing fault)
Input Under Voltage : (Auto Recovery Type) To be checked at 10% load. Output shuts OFF when input voltage is falls down below 185vac.
Input Over Voltage : (Auto Recovery Type) To be checked at 10% load. Output shuts OFF when input voltage goes beyond 264vac.
Over Temperature : 900c + 50c (Factory Test only)
Transient Response : Output should recover within 10ms for 50% step load change.
Operating Temperature: High : 550C Operating. Derating 2.5 % per degree C
beyond 500C output current is58A.(Unit is in OFF condition to be switched ON for last 1/2 hour to take the reading), Low : - 10 % Operating. (Unit is in OFF condition to be switched ON for last 1/2 Hr